Related Links

Case Studies

KwikCHILL Chiller Hire Range

KwikCHILL chiller hire units

KwikCHILL 30

Chiller Hire KwikCHILL 30
Cooling output

33kw

KwikCHILL 50

Chiller Hire KwikCHILL 50
Cooling output

52kw

KwikCHILL 60

Chiller Hire KwikCHILL 60
Cooling output

65kw

KwikCHILL 80

Chiller Hire KwikCHILL 80
Cooling output

82kw

KwikCHILL 100

Chiller Hire KwikCHILL 100
Cooling output

125kw

KwikCHILL 120

Chiller Hire KwikCHILL 120
Cooling output

130kw

KwikCHILL 170

Chiller Hire KwikCHILL 170
Cooling output

170kw

KwikCHILL 200

Chiller Hire KwikCHILL 200
Cooling output

211kw

KwikCHILL 250

Chiller Hire KwikCHILL 250
Cooling output

258kw

KwikCHILL 370

Chiller Hire KwikCHILL 370
Cooling output

371kw

KwikCHILL 500

Chiller Hire KwikCHILL 500
Cooling output

500kw

KwikCHILL 750

Chiller Hire KwikCHILL 750
Cooling output

750kw

Eurovent Certified Performance - Environment Friendly R407C

Chiller Hire Model Summary

Specifications For Chillers Below 170kW
KwikCHILL Model   30 50 60 80 100 120
Cooling capacity @ 30°C Ambient air temperature
7°C flow / 12°C return ΔT 5°C
kW 33.6 52.6 65 82.3 125 130
ESEER at Eurovent conditions   2.90 3.44   3.61    
Min. leaving water temperature °C -4 -12   -12    
Max. leaving water temperature °C +12 +15   +15    
Sound pressure level(10m) dB (A) 51 52   54    
Typical Water Flow Rate L/s 1.64 2.51   3.93    
Water Connections in 1" Camlock 2" Bauer   2" Bauer    
Available Head Pressure kPa 70.6 191.6   162.1    
Water Buffer Tank Volume L 100 370   410    
Expansion Tank Volume L 35 25   25    
Electrical Data v/ph/Hz 400/3/50 415/3/50   415/3/50    
Generator Size Recommended kVA 45 75   100    
Length (X) mm 1300 3560   3965    
Width (Y) mm 1580 1230   1230    
Height (Z) mm 2111 2600   2600    
Specifications For Chillers 170kW & Above
KwikCHILL Model   170 200 250 370 500
Cooling capacity @ 30°C Ambient air temperature
7°C flow / 12°C return ΔT 5°C
kW 170.1 211 257.1 371.8 491.4
ESEER at Eurovent conditions   3.88   3.88 3.56 3.76
Min. leaving water temperature °C -12   -12 -12 -12
Max. leaving water temperature °C +15   +15 +15 +15
Sound pressure level(10m) dB (A) 57   63 65 66
Typical Water Flow Rate L/s 8.13   12.29 17.77 23.49
Water Connections in 3" Bauer   3" Bauer 4" Bauer 4" Bauer
Available Head Pressure kPa 162.1   127.5 153.4 120.2
Water Buffer Tank Volume L 570   570 600 600
Expansion Tank Volume L 35   35 50 50
Electrical Data v/ph/Hz 415/3/50   415/3/50 400/3/50 400/3/50
Generator Size Recommended kVA 200   300 450 550
Length (X) mm 4155   4155 6090 6090
Width (Y) mm 2440   2480 2530 2530
Height (Z) mm 2600   2840 2590 2590

Useful Links

Credit Account Application Do you operate from Multiple Locations? Need a single point of contact for HVAC rental requirements, our dedicated National Accounts team can help Safe Hire Certified Call us today for a free server room air conditioning survey - 0500 526 696

Call Us Free For All Your Temperature Control Hire Needs

Call us for free

Call 0500 526 696 and you will be in touch with an industrial steam boiler rental, heating boiler hire, chiller hire, portable air conditioner hire, evaporative cooling, portable heater, space heating or space cooling specialist who will discuss and understand your requirements for temporary cooling and heating or drying application, arrange site visits where necessary and provide you with a competitive quotation for our hire products and services.

Understanding your rental needs and providing a competitive solution.

Same day service

For over 148 years WatkinsHIRE have understood that it takes more than innovative, high performance temperature control rental products and superior technical service to help our customers, end users & facility managers compete and win in today's global marketplace. It takes a total commitment to understanding your cooling, heating and drying needs and the ability to provide the right temperature control rental solutions every time.